This is a sample report for A&A Certified Home Inspection Termite & Pest Control Company.
A& A Certified15922 Paisley LaneBowie, Maryland 20716 301-218-3550 |
|||
| Customer A&A Home and Pest Customer |
|||
| Inspected Property 321 Main St Your City, MD 20900 |
|||
| Real Estate Agent |
|||
|
|||
|
Inspection Date
7/26/2006 |
|||
|
Weather: |
Report ID: 321 Main St |
||
|
Temperature: |
Inspected By
Nola Bayemake |
||
| Date: 7/26/2006 | Time: 1:39 PM | Report ID: 321 Main St |
| Property: 321 Main St Yourtown, Md 20900 |
Customer: A&A Home and Pest Customer |
Real Estate Professional: |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
| Age Of Home: Over 25 Years | Client Is Present: Yes | Radon Test: No |
| Water Test: Yes | Weather: Hot and Humid | Temperature: Over 65 |
| Rain in last 3 days: Yes |
| Viewed Roof Covering From: Ground | Roof-Type: Gable Shed | Roof Ventilation: Gable vents |
| Method used to observe attic: From Entry | Roof Structure: 2 X 4 Rafters | Ceiling Structure: 2X4 |
| Method used to observe Crawlspace: No crawlspace | Foundation: Masonry block | Floor Structure: 2 X 6 |
| Floor System Insulation: NONE | Wall Structure: Masonry | Operable Fireplaces: One |
| Types of Fireplaces: Conventional | Number of Woodstoves: None |
| 1.0 | Foundations (If all crawlspace areas are not inspected, provide an explanation.) Comments: Inspected |
| 1.1 | Grading and Drainage Comments: Inspected, Not Functioning or in need of repair 1. Visible signs of water intrusion in the basement are present along the block wall. Water intrusion if not corrected can lead to other problems including mold and cause excessive moisture to floor system that can lead to deterioration and increased repair cost.. I recommend further investigation or correction by a qualified licensed contractor or water infiltration specialist. 2. As a result of the water intrusion, coming from the rear and right side of the property, I do recommend outside water proofing. 3. Once the outside water proofing is complete, a French drain will have to be installed in the lower basement.
|
| 1.2 | Roof Covering (If the roof is inaccessible, report the method used to inspect.) Comments: Inspected, Not Functioning or in need of repair The roof has not aged evenly, signs of wear and tear noted on shingles, I recommend roof replacement.
|
| 1.3 | Roof Structure and Attic (If the attic is inaccessible, report the method used to inspect.) Comments: Not Functioning or in need of repair 1. Rear roof starter board and facial boards be replaced due to wood rot. 2. Rear gutters be replaced, and down-spout at the front right be connected to drain hose. 3. Rear right eave board, replace due to wood rot damage
|
| 1.4 | Walls (Interior and Exterior) Comments: Inspected, Not Functioning or in need of repair 1. Sunroom exterior vinyl covering wall, the entire wall and all the wood used for it's construction be replaced, powder post, carpenter ants damage to 2x6 wood found. 2. There are vertical cracks on the right side bearing wall. These cracks have developed as a result of movements, while the cracks are considered hair line cracks at the moment, if these cracks persist any further, corrective action should be taken by licensed professional.
|
| 1.5 | Ceilings and Floors Comments: Inspected, Not Functioning or in need of repair Sunroom ceiling, molds found, (A) provide adequate ventilation in the area (B) Clean molds surface with the appropriate solution.
|
| 1.6 | Doors (Interior and Exterior) Comments: Inspected, Not Functioning or in need of repair 1. Sub-basement, replace sliding door. |
| 1.7 | Windows Comments: Inspected 1. Budget to replace all windows over time. Chipping and peeling paint, and windows with single pane. 2. Lower level basement, replace window with missing pane. 3. Rear left window, replace damage window top frame.
|
| 1.8 | Fireplace/Chimney Comments: Inspected, Not Functioning or in need of repair Fire place, install new functional damper.
|
| 1.9 | Porches, Decks and Carports (Attached) Comments: Not Present |
| 1.10 | Other Comments: Not Functioning or in need of repair 1. Lower level basement, No registers to heat or cool the area, to be installed. 2. Re-construct walk way over time, walkway slab has settled and cracked. 3. Chimney, install missing chimney cap, to prevent or to control water getting into the Furnace or fire place. 4. make all smoke detectors functional.
|
| Electrical Service Conductors: Overhead service | Panel Capacity: 125 AMP | Panel Type: Circuit breakers |
| Electric Panel Manufacturer: CUTLER HAMMER | Branch Wire 15 and 20 AMP: Copper | Wiring Methods: Romex Conduit |
| 2.0 | Service Entrance and Panels Comments: Inspected, Not Functioning or in need of repair 1. Upgrade electrical power coming to the property to 200 amps, 2. Change all wall switches and two prongs outlets. 3. Lover level basement, replace defective out let.
|
| 2.1 | Branch Circuits - Connected Devices and Fixtures (Report as in need of repair the lack of ground fault circuit protection where required.) Comments: Inspected |
| Heat Type: Forced Air | Energy Source: Gas | Heat System Brand: HEIL |
| Number of Heat Systems (excluding wood): One | Ductwork: Non-insulated | Filter Type: Disposable |
| Filter Size: 16x25 | Cooling Equipment Type: Air conditioner unit | Cooling Equipment Energy Source: Electricity |
| Central Air Manufacturer: HEIL | Number of AC Only Units: One |
| 3.0 | Heating Equipment Comments: Not Inspected |
| 3.1 | Cooling Equipment Comments: Inspected, Not Functioning or in need of repair 1. Parts of the A/C unit is buried in the ground, system be cleared of all debris and dirt. 2. A/C unit has no disconnect switch. Once you upgrade the electrical service, install the A/C unit disconnect switch.
|
| 3.2 | Ducts And Vents Comments: Inspected, Not Functioning or in need of repair Have all air ducts cleaned, excessive dusting found inside ducts.
|
| Water Source: Public | Water Filters: None | Plumbing Water Supply (into home): Copper |
| Plumbing Water Distribution (inside home): Copper PVC | Washer Drain Size: Not visible | Plumbing Waste: Cast iron |
| Water Heater Power Source: Gas (quick recovery) | Water Heater Capacity: 40 Gallon (1-2 people) | Manufacturer: RICHMOND |
| 4.0 | Water Supply System AND Fixtures Comments: Inspected |
| 4.1 | Drains, Wastes, Vents Comments: Inspected, Not Functioning or in need of repair Hallway bathroom, sink vanity, replace sink trap, corrosion found.
|
| 4.2 | Water Heater Equipment (Report as in need of repair those conditions specifically listed as recognized hazards by TREC Rules) Comments: Inspected, Not Functioning or in need of repair 1. Front hose bib, leakage noted, plumber to repair or replace new hose bib valve head. 2. Hot water heater, install extension to relief valve. 3. Hot water heater, replace cold line shut off valve due to calcium build-up around valve head.
|
| 4.3 | Hydro-Therapy Equipment Comments: Not Present |
| Dishwasher Brand: FRIGIDAIRE | Disposer Brand: BADGER | Range/Oven: FRIGIDAIRE |
| Exhaust Fan Types: None | Dryer Power Source: 220 Electric | Dryer Vent: Flexible Vinyl |
| 5.0 | Dishwasher Comments: Not Inspected |
| 5.1 | Food Waste Disposer Comments: Inspected |
| 5.2 | Range Hood Comments: Not Functioning or in need of repair Install a range hood.
|
| 5.3 | Ranges/Ovens/Cooktops Comments: Not Inspected |
| 5.4 | Microwave Cooking Equipment Comments: Not Present |
| 5.5 | Trash Compactor Comments: Not Present |
| 5.6 | Bathroom Exhaust Fans and/or Heaters Comments: Inspected |
| 5.7 | Whole House Vacuum Systems Comments: Not Present |
| 5.8 | Garage Door Operators Comments: Not Present |
| 5.9 | Door Bell and Chimes Comments: Inspected |
| 5.10 | Dryer Vents Comments: Not Present |
| 5.11 | Other Built-in Appliances Comments: Not Present |
| 6.0 | Lawn Sprinklers Comments: |
| 6.1 | Swimming Pools and Equipment Comments: |
| 6.2 | Outbuildings Comments: |
| 6.3 | Outdoor Cooking Equipment Comments: |
| 6.4 | Gas Lines Comments: |
| 6.5 | Water Wells (A coliform analysis is recommended.) Comments: |
| 6.6 | Septic Systems Comments: |
| 6.7 | Security Systems Comments: |
| 6.8 | Fire Protection Equipment Comments: |
![]() A& A Certified
15922 Paisley Lane |
|
Customer |
|
Home |
|
This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the home.
This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.
| 1.1 | Grading and Drainage | |
| Inspected, Not Functioning or in need of repair | ||
| 1.2 | Roof Covering (If the roof is inaccessible, report the method used to inspect.) | |
| Inspected, Not Functioning or in need of repair | ||
|
The roof has not aged evenly, signs of wear and tear noted on shingles, I recommend roof replacement. |
||
| 1.3 | Roof Structure and Attic (If the attic is inaccessible, report the method used to inspect.) | |
| Not Functioning or in need of repair | ||
|
1. Rear roof starter board and facial boards be replaced due to wood rot. 2. Rear gutters be replaced, and down-spout at the front right be connected to drain hose. 3. Rear right eave board, replace due to wood rot damage |
||
| 1.4 | Walls (Interior and Exterior) | |
| Inspected, Not Functioning or in need of repair | ||
|
1. Sunroom exterior vinyl covering wall, the entire wall and all the wood used for it's construction be replaced, powder post, carpenter ants damage to 2x6 wood found. 2. There are vertical cracks on the right side bearing wall. These cracks have developed as a result of movements, while the cracks are considered hair line cracks at the moment, if these cracks persist any further, corrective action should be taken by licensed professional. |
||
| 1.5 | Ceilings and Floors | |
| Inspected, Not Functioning or in need of repair | ||
|
Sunroom ceiling, molds found, (A) provide adequate ventilation in the area (B) Clean molds surface with the appropriate solution. |
||
| 1.6 | Doors (Interior and Exterior) | |
| Inspected, Not Functioning or in need of repair | ||
|
1. Sub-basement, replace sliding door. |
||
| 1.7 | Windows | |
| Inspected | ||
|
1. Budget to replace all windows over time. Chipping and peeling paint, and windows with single pane. 2. Lower level basement, replace window with missing pane. 3. Rear left window, replace damage window top frame. |
||
| 1.8 | Fireplace/Chimney | |
| Inspected, Not Functioning or in need of repair | ||
|
Fire place, install new functional damper. |
||
| 1.10 | Other | |
| Not Functioning or in need of repair | ||
|
1. Lower level basement, No registers to heat or cool the area, to be installed. 2. Re-construct walk way over time, walkway slab has settled and cracked. 3. Chimney, install missing chimney cap, to prevent or to control water getting into the Furnace or fire place. 4. make all smoke detectors functional. |
||
| 2.0 | Service Entrance and Panels | |
| Inspected, Not Functioning or in need of repair | ||
|
1. Upgrade electrical power coming to the property to 200 amps, 2. Change all wall switches and two prongs outlets. 3. Lover level basement, replace defective out let. |
||
| 3.1 | Cooling Equipment | |
| Inspected, Not Functioning or in need of repair | ||
|
1. Parts of the A/C unit is buried in the ground, system be cleared of all debris and dirt. 2. A/C unit has no disconnect switch. Once you upgrade the electrical service, install the A/C unit disconnect switch. |
||
| 3.2 | Ducts And Vents | |
| Inspected, Not Functioning or in need of repair | ||
|
Have all air ducts cleaned, excessive dusting found inside ducts. |
||
| 4.1 | Drains, Wastes, Vents | |
| Inspected, Not Functioning or in need of repair | ||
|
Hallway bathroom, sink vanity, replace sink trap, corrosion found. |
||
| 4.2 | Water Heater Equipment (Report as in need of repair those conditions specifically listed as recognized hazards by TREC Rules) | |
| Inspected, Not Functioning or in need of repair | ||
|
1. Front hose bib, leakage noted, plumber to repair or replace new hose bib valve head. 2. Hot water heater, install extension to relief valve. 3. Hot water heater, replace cold line shut off valve due to calcium build-up around valve head. |
||
| 5.2 | Range Hood | |
| Not Functioning or in need of repair | ||
|
Install a range hood. |
||
Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.
|
INVOICE |
| A& A Certified
15922 Paisley Lane Bowie, Maryland 20716 301-218-3550 Inspected By: Nola Bayemake |
Inspection Date: 7/26/2006
Report ID: 321 Main St |
| Customer Info: | Inspection Property: |
| A&A Home and Pest Customer
Customer's Real Estate Professional: |
321 Main St Yourtown, MD 20900 |
Inspection Fee:
| ||||
Tax $0.00 | ||||
| Total Price $0.00 |
Payment:
A&A Certified Home Inspection Company
15922 Paisley
Lane Mitchellville, MD 20716
301-218-3550 / 301-218-3551
Fax 301-218-3459
Inspection Agreement
(Read Carefully)
Name
A&A Home and Pest Customer
|
Inspection
Address 321 Main St Yourtown MD 20900 |
It is understood and agreed that this visual inspection will be conducted on readily accessible areas of the building and is limited to visual inspection of apparent condition existing at the inspection only. This report is not intended to be exhaustive, nor to imply that every component was inspected, nor to imply that every possible defect was discovered. It is intended to assist the Client in evaluating the overall condition of the building. This report is conducted to the best of the inspector’s knowledge and ability; however, No Express or Implied Warranty is Given Concerning the Opinions Expressed by the Inspector or Concerning the Components that were inspected. The Client is urged to follow the inspector during the inspection, to take notes, and ask questions, however, A&A Certified assumes no liability for Clients safety; thereby urging the Client to evaluate whether it is safe to accompany the Inspector or not.
Our Inspector will cover the following area and components
| Structural Electrical Insulation/Ventilation Kitchen/Appliances Walls/Ceiling Roof/Attic Gutter/Drainage Exterior Finish |
Basement/Crawl Space Heating/Cooling Plumbing Floors Windows/Doors Fireplace/Chimney General Summary Paint Condition |
Probable expenses to be incurred within the next three- (3) years
Latent and concealed defect and deficiencies are excluded from this inspection, no disassembly of equipment, opening of wall, floors, ceiling excavation, removal of carpet, plated or cover will be performed.
Note: This Inspection does not address environmental issue to include but not limited to lead basePaint asbestos and mold/mildew.
However, peeling and chipping paint could bean indication of lead problems. Mold/mildew- a sign of serious moisture problem. In each of these instances, we recommend testing and further evaluation. Call our office for more information.
Leakage’s that only occur under unusual weather condition to basement, walls and roof are not predictable, as well as stains that have been painted over or damage that has been repaired will not be evident at the time of the inspection.
Poor or improper wiring and connections that are not readily visible
because they are sealed within junction boxes are not dismantled.
It
is understood and agreed that the company is not an insurer and that
the visual inspection and report are not intended or to be construed
as a guarantee or warranty of the adequacy, performance, or condition
of the structure and it’s components. In the event
a problem develops with any component Inspected, the Client must
contact us first prior to having any corrective measure taken. Failure
to do so relieves A&A Certified of any responsibility concerning
that component.
In the event that the company and/or its employees are found liable due to breach of contract, the breach thereby shall be submitted to final and binding arbitration under the Expedited Arbitration Rules of National Academy of Conciliators. Any disputed, controversy, interpretation or claim including claims for, but not limited to, breach of contract, any form of negligence, fraud or misrepresentation or any other theory of liability arising out of from or related to, this inspection or inspection report shall be submitted to final and binding arbitration “ under the rule and procedures of Expedited Arbitration of Home Inspection Disputes of Construction Arbitration Service, Inc.” The decision of the Arbitration appointed thereunder shall be final and binding and judgement on the award may be entered in any Court of Competent jurisdiction. The parties acknowledge that any damages that Client may incur as a result of a breach of this contract against A&A Certified Home Inspection Company, it’s agents, employees, successor or assign, under any and all legal or equitable cause or causes of action in lesser of amount paid to A&A Certified Home Inspection Company by the Client or $500.00 The Client hereby waives any claims, releases and exempts the company and it’s agents and employees of and from all liability for the cost of replacing any unreported defect and any consequential damage or personal injury of any nature.
I hereby acknowledge acceptance and understanding of the agreement:
Client Signature_______________________ Date__________________
Inspectors Signature__________________ Date___________________
Total Fee $ 0.00
Paid by:
q Cash
q Money
Order
2. As a result of the water intrusion, coming from the rear and right side of the property, I do recommend outside water proofing.
3. Once the outside water proofing is complete, a French drain will have to be installed in the lower basement.